Common faults of pressure transmitter
1. If the pressure goes up, the transmitter output will not go up: In this case, check whether the pressure interface is leaking or blocked, if it is normal. Check the wiring mode, if the wiring is correct. Next, check the power supply, if it is normal. Please check whether there is any output at the zero position of the sensor, or simply pressurize it to see if the output has changed. If there is a change, the sensor is not damaged; if there is no change, the sensor is confirmed to be damaged. Other reasons for this situation may also be instrument damage (such as PLC range setting problems, etc.).
2.增压变送器输出不变,然后增压变送器输出突然变化,泄压变送器回不到零位。这种现象可能是压力传感器密封圈造成的,在我们客户的使用中遇到过很多次。一般是因为密封圈的规格问题(太软或者太厚)。当传感器拧紧时,密封圈被压入传感器的压力口,堵住传感器,加压时压力介质进不去。但是当压力很大时,密封圈突然爆开,压力传感器因压力而发生变化。当压力再次降低时,密封圈回位堵住压力口,残余压力无法释放, 所以传感器的零位下不来了。消除这种原因的方法是拆下传感器,直接检查零位是否正常。如果正常,请更换合适的密封圈,然后重试。
3.发射机的输出信号不稳定
失败的原因如下:
(1)由于安装位置的振动,传感器振动严重。
(2)仪表或压力传感器的抗干扰能力不强。
(3)压力源本身就是不稳定压力。
(4)、传感器接线不牢固
(5)、传感器故障
4.发射器通电,无输出。
失败的原因如下:
(1)、线路错误(需要同时检查二次仪表和传感器)
(2)电源无输出或电源不匹配。
(3)导体本身开路或短路
(4)仪器损坏或不匹配。
(5)传感器损坏
5、变送器和指针压力表控制偏差大时,首先确认偏差正常,然后确认偏差范围正常,确认误差范围正常的方法:
计算压力计的误差值。比如压力表的量程是30bar,精度是1.5%,小刻度是0.2bar,正常误差是30bar*1.5%+0.2*0.5(目测误差)=0.55bar。
6.压力变送器的误差值。
比如压力传感器量程为20bar,精度为0.5%,仪器精度为0.2%,正常误差为:20bar*0.5%+20bar*0.2%=0.18bar,误差值大的设备误差范围为准。在上面的例子中,传感器和变送器之间的偏差在0.55bar以内可视为正常
如果偏差很大,就用高精度的仪器(至少这个仪器要比压力表和传感器的精度高)做参考。
7.微差压变送器安装位置对零输出的影响;
由于微差压变送器的量程很小,变送器中敏感元件的自重会影响微差压变送器的输出,所以微差压变送器安装时的零点变化是正常的。安装时,变送器的压力敏感部分应垂直于重力方向。如果安装条件有限,应在安装固定后将变送器的零位调整到标准值。